|
Wall:
|
AWWA D110-04 Code
|
Wrapped Prestressed Tank
|
AWWA D115-06 Code
|
Tendon Prestressed Tank
|
|
Minimum Thickness
|
3.5.4
|
as low as 3.5" - depending on wall type I, II, III or IV
|
3.7.3
|
9", however 11" -12" is most common
|
|
Required minimum horizontal residual compression from prestressing
|
3.4.2.2
|
200 psi for wall above grade, 50 psi for wall below grade - only concrete core wall within the wrapping is prestressed - shotcrete coatings on prestressing steel has no residual compression and is usually in tension
|
3.7.4.1
|
200 psi for wall above grade, 100 psi for wall below grade - entire wall thickness is prestressed with minimum residual compression
|
|
Required minimum vertical residual compression from prestressing
|
3.5.3
|
200 psi only on concrete core wall within the wrapping is prestressed - shotcrete coatings on prestressing steel has no residual compression
|
3.7.5
|
200 psi for above grade, 125 psi for below grade - entire wall thickness is prestressed with minimum residual compression
|
|
Sheet steel diaphragms provide watertightness?
|
3.5.6
|
yes - if wall type II, III or IV. If not vertically post-tensioned wall must have a steel diaphragm. Vertical rebar may be eliminated depending on design.
|
|
steel diaphragms not used or required as quality concrete is impermeable
|
|
Steel sheet diaphragms provide flexural reinforcement?
|
2.5.1.3, 2.9.1
|
26 gauge steel sheets relied on for watertightness and vertical flexural reinforcement - field joints require field-applied sealants, type IV walls require field-applied sealants at form tie holes
|
|
steel diaphragms not used or required as quality concrete is impermeable
|
|
Inside face concrete cover on vertical mild reinforcement
|
3.5.4.2, 3.5.6.2
|
1" on steel sheet diaphragm and rebar
|
3.11
|
1.5" on rebar if not two-way prestressed, 1" on rebar if two-way prestressed
|
|
Precast panel misalignment?
|
5.2.7
|
up to 3/8" misalignment allowed for precast wall segments,
|
|
wall segments are cast-in-place, no misalignment possible
|
|
Vertical mild reinforcement ratio
|
3.5.6
|
0.0025 each face (steel diaphragm is included in ratio for type II, III and IV walls)
|
|
no minimum may be required if prestressed and depending on concrete stresses
|
|
Vertical prestressing protection
|
|
"unbonded grouted" system - grade 150 bar in a PVC duct with epoxy grout, vertical prestressing only used on type I tanks
|
1.3
|
5" minimum cover of bi-axially precompressed concrete, HDPE duct and coating in accordance with PTI and ACI standards
|
|
Horizontal prestressing protection
|
5.3.3.3.4
|
Sacrificial galvanizing on wire with one inch of non-prestressed shotcrete cover. Shotcrete cover goes into tension as it shrinks and when tank is filled, cover can delaminate, leakage source difficult to locate - water migrates beneath the shotcrete.
|
1.3
|
3" minimum cover of bi-axially precompressed concrete, HDPP duct, high-performance grouting in accordance with PTI and ACI standards
|
|
Wall construction methods
|
1.1.1
|
four different wall types that can result in sole sourcing of a particular type
|
|
cast-in-place construction is non-proprietary
|
|
Shotcete cover on metal diaphragms
|
3.5.4.2, 3.5.6.2
|
for diaphragms, 1" inside face cover and 0.5" cover on outside prior to wrapping
|
|
|